EL
ErrorLib
Brands
||
  1. Home
  2. Allen-Bradley
  3. PowerFlex 4 Adjustable Frequency
  4. F43
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

F43

Phase VW Short

Allen-Bradley · PowerFlex 4 Adjustable Frequency

What does F43 mean?

A short circuit condition has been detected between motor phases V and W, or in the wiring connecting drive output terminals V and W to the motor. This indicates an unintended low-resistance path between these phases.

Common Causes

  • Short circuit between phase V and phase W windings in the motor.
  • Internal short circuit in the drive's output power module.
  • Power cable damage causing conductors V and W to short.
  • Incorrect motor connection or wiring error.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Disconnect the motor from the drive output terminals (U, V, W).

  2. 2

    Measure resistance between drive output terminals V and W with the motor disconnected; expect an open circuit (infinite resistance) if no internal drive fault.

  3. 3

    Measure resistance between motor phases V and W; expect a low resistance reading (continuity across the motor winding).

  4. 4

    Inspect the wiring between drive output terminals V, W and motor phases V, W for any physical damage or direct short circuits.

Browse all codes in this manual (24)
Verified technical data. Last updated: April 2026

Related Faults

F100Parameter ChecksumF12HW OverCurrentF122I/O Board Fail
Source: Allen-Bradley PowerFlex 4 Adjustable Frequency
Open Manual (Page 15)Search more codes in this manual