Allen-Bradley · PowerFlex 4 Adjustable Frequency
A software-detected overcurrent condition has occurred, meaning the instantaneous output current has exceeded the trip level configured by parameter A098 [SWCurrent Trip]. This is a configurable threshold for current monitoring.
Click steps to track your progress.
Verify the load requirements of the motor and ensure they are within the drive's continuous operating current capabilities.
Review and adjust parameter A098 [SWCurrent Trip] to ensure it is appropriately set for the application, not exceeding DriveAmps * 2.
Increase acceleration time (parameter P039 [Accel Time1] or A067 [Accel Time2]) to reduce peak currents during motor startup.