Allen-Bradley · PowerFlex 40 Adjustable Frequency
This fault occurs when an analog input, configured to fault upon signal loss, loses its expected input signal. This means the drive is no longer receiving a valid reference from the analog source (e.g., 0-10V or 4-20mA). This is an Auto-Reset/Run type fault configurable with parameters A092 and A093.
Click steps to track your progress.
Measure the voltage (for 0-10V) or current (for 4-20mA) at the drive's analog input terminals (e.g., AIN1, AIN2) using a multimeter.
Verify the integrity of the analog input signal wiring by checking continuity and insulation resistance from the signal source to the drive terminals.
Confirm drive parameter P065 [Analog In Loss Act] is set to the desired fault action (e.g., 'Fault') and its trip level.
Inspect the external analog signal source device (e.g., transducer) for power supply and proper operation, measuring its output directly.
Check the drive's internal diagnostics for real-time analog input values to differentiate between external signal loss and drive input circuit failure.