Allen-Bradley · PowerFlex 40 Adjustable Frequency
This fault signifies a loss of incoming AC line power or a significant low voltage condition on the AC input. It indicates the drive's inability to maintain operation due to insufficient input power.
Click steps to track your progress.
Measure the incoming AC line voltage (L1-L2, L2-L3, L3-L1 for 3-phase, L1-N for 1-phase) at the drive's input terminals using a multimeter.
Inspect all upstream circuit breakers and fuses for tripped conditions or blown elements and reset/replace as necessary.
Verify the torque on the incoming AC power wiring connections to the drive's L1, L2, L3 terminals and the upstream disconnect.
Check for sustained voltage sags on the utility grid using a power quality meter if the fault is intermittent or occurs during heavy load transients.
Examine the main contactor (if present upstream of the drive) for proper coil voltage and contact integrity.