Allen-Bradley · PowerFlex 40 Adjustable Frequency
This fault indicates that the drive has exhausted its configured number of automatic restart attempts (parameter A092 [Auto Rstrt Tries]) after a previous fault. The underlying cause of the initial fault must be addressed before the drive can restart.
Click steps to track your progress.
Identify and troubleshoot the *original* fault code that triggered the auto-restart sequence by checking the drive's fault history log.
Verify drive parameter A092 [Auto Rstrt Tries] is set to an appropriate number for the application, or '0' if auto-restart is not desired.
Monitor the operating conditions and drive display after a restart to observe if the original fault reoccurs and determine its cause.
Inspect the mechanical load and motor to ensure no persistent physical obstruction or electrical issue is present, which would immediately re-trip the drive.
If the original fault was intermittent, consider adjusting parameter A090 [Auto Rstrt Delay] to allow more time for transient conditions to clear before restarting.