Allen-Bradley · PowerFlex 40 Adjustable Frequency
This fault is triggered when the incoming AC line voltage drops below the drive's acceptable operating range. This can be caused by a sustained low voltage condition or a momentary power sag. This is an Auto-Reset/Run type fault configurable with parameters A092 and A093.
Click steps to track your progress.
Measure the incoming AC line voltage (L1-L2, L2-L3, L3-L1 for 3-phase, L1-N for 1-phase) at the drive's input terminals and compare to drive specifications.
Monitor the DC bus voltage (often accessible via drive display) during operation to observe its behavior relative to the Undervoltage trip threshold.
Check the torque of the wiring connections at the drive's L1, L2, L3 input terminals and upstream disconnect.
Consult local power company or plant electrical staff regarding potential grid voltage instability or heavy load switching events.
If a sag is suspected, use a power quality analyzer to log input voltage over time to capture transient events.