Allen-Bradley · PowerFlex 40 Adjustable Frequency
This fault detects a short circuit condition between motor phases U and V at the drive output. This implies an insulation failure within the motor windings or a direct short in the cabling connecting the drive to the motor.
Click steps to track your progress.
Disconnect the motor cables (U, V, W) from the drive output terminals. Use an ohmmeter to measure resistance between motor cable phase U and phase V conductors.
Use an ohmmeter to measure resistance directly at the motor terminals between phase U and phase V, after disconnecting from the cable.
Visually inspect the motor cable's insulation integrity, focusing on the conductors for phase U and V, especially at bends or connection points.
Inspect the motor terminal box and the drive output terminal block for phases U and V for any loose strands, conductive debris, or signs of arcing between them.
Check for correct wire gauge and termination practices to ensure no physical contact or potential for shorting between phase U and V.