Allen-Bradley · PowerFlex 40 Adjustable Frequency
This fault detects a short circuit condition between motor phases U and W at the drive output. This implies an insulation failure within the motor windings or a direct short in the cabling connecting the drive to the motor.
Click steps to track your progress.
Isolate power to the drive and motor. Disconnect motor leads U and W from the drive output terminals (T1, T3).
Measure resistance between motor phases U and W at the motor terminal block using a multimeter (ohmmeter). Expect an open circuit or very high resistance (>20 MΩ).
Perform a megger test (insulation resistance test) between motor phases U and W at the motor terminal block at 500VDC or 1000VDC. Expect >100 MΩ.
Visually inspect motor cables for signs of insulation damage, crimping, or water ingress. Inspect drive output terminals for debris or arcing evidence.
If the motor and cables test good, disconnect the motor cable at the drive output and measure resistance between drive output terminals U and W. If shorted, replace the drive.