F33

Auto Rstrt Tries

Allen-Bradley · PowerFlex 4M Adjustable Frequency

What does F33 mean?

The drive has attempted to automatically reset a fault and restart the programmed number of times (set by A451) without success. This indicates a persistent underlying issue that the auto-restart feature cannot resolve, preventing the drive from resuming operation.

Common Causes

  • A persistent underlying fault condition (e.g., overcurrent, undervoltage) is recurring, causing the drive to fault repeatedly.
  • Parameter A451 (Auto Restart Tries) is set too low, preventing the drive from successfully clearing a transient fault.
  • Intermittent activation of an external input (e.g., safety circuit, E-stop) leading to repeated fault conditions.
  • Environmental instability (e.g., fluctuating input power, extreme temperatures) causing recurring, non-permanent faults.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Access the drive's fault history log and identify the specific fault code that occurred immediately before F33.

  2. 2

    Temporarily disable auto-restart (set A451 to 0) and monitor the drive for the recurring root fault to diagnose its origin.

  3. 3

    Inspect external control wiring and devices connected to the drive's digital inputs for intermittent contact issues.

  4. 4

    Monitor the drive's input supply voltage (e.g., at terminals R, S, T) for stability during operation, noting any sags or fluctuations.

  5. 5

    Review parameter A451 (Auto Restart Tries) and consider increasing it if the underlying fault is confirmed to be transient and non-critical.