Allen-Bradley · PowerFlex 4M Adjustable Frequency
This fault indicates that the drive has been commanded to restore its parameters to factory default values, typically through a user action or system command. While not a malfunction, it means previous custom configurations are lost, which could lead to incorrect operation if not re-programmed.
Click steps to track your progress.
Identify the method by which parameters were defaulted (e.g., HMI button sequence, network command, specific parameter setting like P1-05).
Upload a previously saved parameter configuration file from backup software to restore settings to the drive.
If no backup exists, manually re-enter all critical motor and application parameters (e.g., P3-08, P3-09, P3-10, P3-11).
Review security settings or user access levels to prevent unauthorized parameter changes or resets.
Perform a full functional test of the drive and connected equipment after parameters are restored and saved.