Allen-Bradley · PowerFlex 700
The drive is not following a commanded deceleration because it is attempting to limit bus voltage. This indicates the DC bus voltage is rising due to regenerative energy, potentially exceeding safe limits and causing the drive to inhibit deceleration.
Click steps to track your progress.
Verify input voltage is within the drive's specified limits.
Verify system ground impedance follows proper grounding techniques.
Disable bus regulation and/or add a dynamic brake resistor and/or extend the deceleration time parameter.