36

Software Overcurrent

Allen-Bradley · PowerFlex 700

What does 36 mean?

The drive output current has exceeded its 1ms current rating, which is typically 200-250% of the drive's continuous rating. This indicates a sudden, high current demand that could be due to excessive load, improper DC boost settings, or excessively high DC brake volts, risking damage to the drive.

Common Causes

  • Software detected current exceeding safety limits.
  • Incorrect current limiting parameter (P1-36).
  • Motor drawing excessive current due to mechanical load.
  • Faulty current sensing circuitry.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check for excess load on the motor.

  2. 2

    Verify the [DC boost setting] parameter is correctly configured.

  3. 3

    Check the [DC brake volts] parameter setting to ensure it is not too high.

Browse all codes in this manual (49)
Verified technical data. Last updated: April 2026

Related Faults

100Parameter Checksum Error101UserSet1 Chksum102UserSet2 Chksum
Source: Allen-Bradley PowerFlex 700
Open Manual (Page 88)Search more codes in this manual