The DC bus voltage has fallen below the minimum threshold (407V DC for 400/480V input, or 204V DC for 200/240V input). This fault indicates an insufficient incoming AC line voltage or a momentary power interruption. This condition can be enabled or disabled via [Fault Config 1] (page 1-46) based on application needs.
Click steps to track your progress.
Monitor the incoming AC line voltage at the drive's input terminals for sags, drops, or power interruptions.
Verify parameter [Fault Config 1] on page 1-46 to ensure the undervoltage fault is configured as desired for the application.