Allen-Bradley · PowerFlex 700
A DPI port has stopped communicating, or a SCANport device was connected to a drive operating DPI devices at 500k baud. This indicates a loss of communication with a connected DPI device, which can prevent control commands or feedback from reaching the drive. The fault code varies depending on which port (1-5) lost communication.
Click steps to track your progress.
If the adapter was not intentionally disconnected, check the wiring to the affected DPI port.
Check the HIM (Human Interface Module) connection.
If an adapter was intentionally disconnected and the [Logic Mask] bit for that adapter is set to "1", set the [Logic Mask] bit for the adapter to "0" to disable this fault.
Replace wiring, port expander, adapters, or Main Control Board as required.