Temperature Difference Error
Beckhoff · EL2904 TwinSAFE Fail-Safe Output Terminal
What does Diag 2 Flash 9 mean?
A significant temperature difference has been detected between internal components of the terminal, such as between different processor boards or specific microcontrollers. This indicates an imbalance in heat distribution or a localized thermal issue that could affect the stability and longevity of the terminal's electronics. Unresolved, it can lead to unreliable operation or component failure.
Common Causes
- Localized hot spot due to component failure (e.g., shorted semiconductor, failing power component) on one part of the board, while another part remains cool.
- Uneven airflow or localized obstruction within the module or cabinet, leading to inefficient cooling of specific internal areas.
- Miscalibrated or faulty temperature sensor on one specific microcontroller (μC1 or μC2) providing incorrect readings compared to another.
- Insufficient thermal paste or improper heat sink contact on a specific processor, leading to poor heat transfer.
- Design or manufacturing defect causing abnormal heat generation or dissipation across different sections of the terminal's PCB.
Repair Steps & Checklist
Click steps to track your progress.
- 1
1. Power down the terminal and visually inspect the circuit board for any signs of localized overheating (e.g., discoloration, burnt components) around microcontrollers μC1 or μC2.
- 2
2. Ensure uniform airflow across the terminal module by verifying no localized obstructions from adjacent components or wiring within the cabinet.
- 3
3. With the terminal powered on and operating (if safe), use an infrared thermometer to measure surface temperatures across different areas of the module's casing, looking for significant localized hot spots.
- 4
4. Verify that the terminal is operating within its specified load limits. An overloaded specific output or internal function could cause localized heating on one component.
- 5
5. If the issue persists despite external checks, the module likely has an internal component failure or thermal design flaw, requiring replacement of the terminal.