The K-bus State variable in TwinCAT has Bit 10 set, indicating that the K-bus output update cycle has not yet completed. This can result in outputs not being set or updated as expected by the PLC program.
Click steps to track your progress.
Evaluate the TwinCAT task time configured for the K-bus. Ensure the task time is sufficiently fast (recommended less than 50 ms) to allow for complete output updates.
Check for high system loading or excessive data traffic on the K-bus that might be delaying the completion of output update cycles.