Beckhoff · EL7201-000x, EL7211-000x EtherCAT Terminals
This Read-Only BOOLEAN object indicates a synchronization error related to the EtherCAT Distributed Clocks (DC) system or SyncManager (SM) events for the Beckhoff EL7201-000x and EL7211-000x EtherCAT Terminals. It reflects the status of object 0x1C32:32, where a TRUE value signifies an active synchronization fault.
Click steps to track your progress.
Verify the EtherCAT master's configuration for the EL7201-000x/EL7211-000x terminals, ensuring the selected synchronization mode (e.g., FreeRun, SM-Synchron, DC-Synchron) is appropriate for the application and correctly parameterized.
Perform a thorough inspection of all EtherCAT network cables and connectors associated with the EL7201-000x/EL7211-000x terminal for signs of damage, proper shielding, secure connections, and correct port assignments.
Access and monitor EtherCAT objects 0x1C33:0B (SM event missed counter) and 0x1C33:0C (Cycle exceeded counter) for the EL7201-000x/EL7211-000x terminal; increasing counts indicate a recurring synchronization problem.
Consult the EtherCAT master's diagnostic interface, event log, or error history for any additional messages or details that might specify the nature or source of the synchronization error affecting the EL7201-000x/EL7211-000x terminal.
If the application utilizes DC-Synchron mode, review the "DC" tab (Distributed Clocks) in the TwinCAT configuration for the EL7201-000x/EL7211-000x terminal, adjusting advanced settings or distributed clock parameters to improve timing stability if necessary.