Bosch Rexroth · IndraDrive MPx02
This non-fatal error indicates that a programmed motion step in a sequence or profile was skipped by the IndraDrive MPx02. This can lead to unexpected machine behavior, loss of synchronization, or incorrect positioning.
Click steps to track your progress.
Review the motion program or sequence to ensure logical flow, correct sequencing, and valid conditions for each step.
Check the communication cycle time between the master controller and the IndraDrive MPx02 to ensure it is fast enough for the application.
Verify parameter settings related to motion execution, such as S-0-0145 (Motion sequence buffer size).
Monitor external interlock signals and their timing to confirm they are not inadvertently causing steps to be skipped.
Update the IndraDrive MPx02 firmware to the latest version to address potential software issues.