Overcurrent
Danfoss · VLT 2800 Variable Speed Drive
What does 13 mean?
The inverter’s peak current limit (approximately 200% of rated output current) has been exceeded. This is a severe, instantaneous overload condition that will cause the drive to trip and alarm after 1-2 seconds. It can indicate a mechanical jam or an incorrectly sized motor/drive.
Common Causes
- Direct short circuit between two output phases (U, V, W) or a ground fault on one of the output phases to the motor cable or motor windings.
- Sudden, severe mechanical jam or impact on the driven equipment, causing instantaneous motor current demand well beyond limits.
- Extremely rapid acceleration (P2-00 set too low) of a high-inertia load, leading to excessive current transients.
- Faulty IGBT power module within the drive, causing a short-through condition.
- Motor cable too long or improperly shielded, leading to high capacitance and surge currents.
Repair Steps & Checklist
Click steps to track your progress.
- 1
1. Power off the drive immediately. Disconnect the motor cables from the drive's output terminals (U, V, W).
- 2
2. Perform an insulation resistance test (megohmmeter, 500VDC or 1000VDC) on each motor phase (U, V, W) to ground, and phase-to-phase to check for short circuits.
- 3
3. Perform a winding resistance test (ohmmeter) on the motor (U-V, V-W, W-U) to confirm balanced windings and absence of phase-to-phase shorts.
- 4
4. Inspect the motor cables for physical damage, pinching, or water ingress that could cause a short.
- 5
5. If the fault clears with the motor disconnected, inspect the mechanical load for any sudden, severe jams or binding that would cause extreme torque demand.
- 6
6. Temporarily increase acceleration time (P2-00) by 50-100% to reduce startup current if the fault occurs during acceleration.