34

HPFB communication fault

Danfoss · VLT 2800 Variable Speed Drive

What does 34 mean?

This communication fault specifically occurs in Profibus versions of the drive. It indicates a problem with data exchange over the Profibus network via the HPFB option card.

Common Causes

  • Incorrect Profibus network configuration (e.g., GSD file mismatch, incorrect DP address P801, or baud rate P802).
  • Physical damage to the Profibus cable (e.g., break, short, shield fault) or loose connection at the HPFB card.
  • Profibus termination resistors are missing, incorrectly placed, or not enabled/disabled properly on the segment.
  • Profibus master (PLC) is not in RUN mode, has a communication fault itself, or is not configured to poll the drive's address.
  • High levels of electromagnetic interference (EMI) corrupting data packets on the Profibus network.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the Profibus GSD file used in the PLC project matches the specific HPFB option card version in the drive.

  2. 2

    Check the drive's Profibus address (P801) and baud rate (P802) against the PLC configuration. Ensure no duplicate addresses on the bus.

  3. 3

    Inspect the Profibus cable for continuity, shorts, and proper shielding connections from the HPFB card to the network segment.

  4. 4

    Confirm that Profibus termination resistors are correctly installed and enabled/disabled at the physical ends of the Profibus segment.

  5. 5

    Check the Profibus master (PLC) diagnostic buffer for specific communication errors related to the drive's address.

  6. 6

    Use a Profibus diagnostic tool (e.g., ProfiTrace) to analyze bus telegrams, identify signal integrity issues, and locate faulty nodes or segments.

Browse all codes in this manual (40)
Verified technical data. Last updated: March 2026

Related Faults

Source: Danfoss VLT 2800 Variable Speed Drive