1379–2819

Internal fault (Specific range)

Danfoss · VLT AutomationDrive FC 301/302

What does 1379–2819 mean?

A general internal fault has occurred within a specific range of internal error codes. This indicates an unspecified internal hardware or software malfunction that requires specialized attention.

Common Causes

  • Transient power supply instability on the internal 5VDC or 3.3VDC rails.
  • Firmware corruption due to an interrupted update procedure or internal memory write error.
  • Component degradation on the main control board (e.g., a failing electrolytic capacitor or integrated circuit).
  • Overheating of internal processing units leading to calculation errors or unexpected behavior.
  • Corrupted configuration data in non-volatile memory (EEPROM or Flash) that affects critical system startup.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Record the exact fault sub-code displayed on the Local Control Panel (LCP) for further analysis.

  2. 2

    Power cycle the drive by disconnecting mains voltage (L1, L2, L3) for at least 60 seconds.

  3. 3

    Verify the drive's internal cooling fan operation and clean any dust from internal heat sinks.

  4. 4

    Measure the internal 24VDC, 5VDC, and 3.3VDC supply voltages on designated test points of the control board.

  5. 5

    Attempt to re-upload the drive's firmware using the specified programming tool and the correct firmware version.

  6. 6

    Backup drive parameters, then perform a factory reset via Parameter P14-22 (Reset options) set to 2 (Load LCP defaults).

Browse all codes in this manual (66)
Verified technical data. Last updated: March 2026

Related Faults

Source: Danfoss VLT AutomationDrive FC 301/302