Internal fault (Specific range)
Danfoss · VLT AutomationDrive FC 301/302
What does 512–519 mean?
A general internal fault has occurred within a specific range of internal error codes. This indicates an unspecified internal hardware or software malfunction that requires specialized attention.
Common Causes
- Undetermined software exception or run-time error within the drive's operating system or application code.
- Transient hardware malfunction on the control board (e.g., a watchdog timer reset, bus error).
- Corruption of critical RAM or flash memory areas due to power instability or electromagnetic interference.
- Failed internal communication between different processors or modules within the drive.
- Component failure (e.g., passive components, ASICs) on the control board leading to unpredictable behavior.
Repair Steps & Checklist
Click steps to track your progress.
- 1
1. Record the exact internal sub-code displayed with the main fault code, as this provides crucial diagnostic information for technical support.
- 2
2. Perform a full power cycle of the drive, waiting at least 60 seconds after disconnecting power before reapplying it.
- 3
3. Attempt to clear the fault using the drive's LCP reset button or parameter P16-90 (Fault Log).
- 4
4. Verify the stability of the input power supply to the drive by measuring L1-L2, L2-L3, L3-L1 voltages at the terminals.
- 5
5. Ensure all option cards are securely seated and their firmware is compatible; if the issue persists, temporarily remove non-essential option cards and retest.