Short circuit
Danfoss · VLT HVAC Basic FC 101
What does 16 mean?
A direct short circuit condition has been detected either within the motor's windings or across its terminal connections. This is a highly critical fault that triggers a trip-lock, requiring a power cycle to reset after the cause is rectified. Operating with a short circuit can cause immediate and irreparable damage to the frequency converter's IGBTs or other power components.
Common Causes
- Direct phase-to-phase short circuit within the motor windings due to insulation failure.
- Loose strands of conductor or foreign metallic objects causing a short circuit at the motor terminal block.
- Severe damage to motor cable insulation, leading to direct conductor-to-conductor contact (phase-to-phase short).
- Drive internal power component (IGBT) failure on the output stage, resulting in a permanent short.
- Incorrect wiring in the motor terminal box, causing a misconnection (e.g., two phases directly connected).
Repair Steps & Checklist
Click steps to track your progress.
- 1
Power off the drive and disconnect input power. Disconnect motor cables from drive output terminals (U, V, W).
- 2
Measure resistance between each pair of motor phase terminals (U-V, V-W, W-U) at the motor. All three readings should be similar and low (e.g., < 1 Ohm for large motors).
- 3
Visually inspect the motor terminal box for loose wires, metallic debris, or damaged insulation between phases.
- 4
Perform an insulation resistance test (megger) phase-to-phase and phase-to-ground on the motor windings.
- 5
If motor and cable tests are clear, a drive internal fault is likely. Contact authorized service personnel for internal diagnosis.