ALARM 30

Motor phase U missing

Danfoss · VLT HVAC Basic FC 101

What does ALARM 30 mean?

The motor phase U connection between the frequency converter and the motor is missing or interrupted. This prevents proper motor operation and can lead to damage if ignored.

Common Causes

  • Loose or disconnected conductor at the drive output terminal U.
  • Loose or disconnected conductor at the motor terminal U.
  • Break or high resistance in the motor cable's U phase conductor.
  • Faulty contactor or circuit breaker in the motor output circuit (if present) for phase U.
  • Failure of the drive's output power stage (e.g., IGBT) specifically for phase U.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Power off the drive and disconnect input power. Visually inspect and tighten connections for the U-phase motor cable at both the drive's U output terminal and the motor's U terminal.

  2. 2

    Measure the resistance of the U-phase motor cable conductor from the drive end to the motor end to check for continuity (expect < 1 Ohm).

  3. 3

    With motor cables disconnected from the drive, measure the resistance between motor terminals U-V, U-W, and V-W. All three values should be balanced and low.

  4. 4

    Check for any external fusing or contactors in the U-phase motor circuit for continuity and proper operation.

  5. 5

    If cable and motor are verified good, the fault indicates a potential internal drive hardware issue with the U-phase output.

Browse all codes in this manual (40)
Verified technical data. Last updated: March 2026

Related Faults

Source: Danfoss VLT HVAC Basic FC 101