68

Safe Stop activated

Danfoss · VLT HVAC Drive FC 102

What does 68 mean?

The Safe Stop function has been activated, bringing the motor to a controlled stop and preventing unintended restart. This is a critical safety feature typically triggered by an external safety input. The drive will remain in this state until the safety input is cleared and a reset commanded.

Common Causes

  • External safety circuit device (e.g., emergency stop button, light curtain, safety gate switch) has been activated.
  • Faulty wiring or short circuit in the external Safe Torque Off (STO) or Safe Stop input (e.g., terminals 37, 38).
  • Internal safety relay failure or component malfunction within the drive's safety circuit.
  • Momentary power sag causing transient activation of the safety input monitoring circuit.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Verify the status of all connected external safety devices (e.g., E-Stop, safety mats, light curtains) are reset and active.

  2. 2

    2. Measure the voltage across the Safe Stop input terminals (e.g., 37 and 38) to confirm expected safety circuit status.

  3. 3

    3. Inspect wiring for the Safe Stop circuit for damage, loose connections, or incorrect termination.

  4. 4

    4. Cycle power to the drive and attempt to reset the fault through the LCP or via the external safety reset input.

Browse all codes in this manual (75)
Verified technical data. Last updated: March 2026