01

No write access to the parameter (Register 0007)

Danfoss · VLT Micro Drive FC 51

What does 01 mean?

An attempt was made to write to a parameter through Holding Register 0007 that is either inherently read-only or currently write-protected. This indicates a parameter that can only be viewed, or one that requires a specific operating state or access level for modification.

Common Causes

  • Attempting to write to a parameter that is inherently read-only (e.g., drive serial number, fault log entries) through Modbus Holding Register 0007.
  • Parameter access level (e.g., Parameter 16-00, 'Access code') is set too low on the drive to allow write operations via communication.
  • The drive is currently running the motor, and the specific parameter (e.g., motor configuration via Parameter 1-20) cannot be modified during operation.
  • A temporary lockout or protection mechanism is active (e.g., during an autotune process via Parameter 8-00, or a safety function engaged).
  • The parameter requires a password to be entered via the LCP or a specific write sequence that isn't being followed by the Modbus master.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify in the drive's communication manual that the target parameter is actually writeable via Modbus Holding Register 0007.

  2. 2

    Set the drive's access level (e.g., Parameter 16-00) to a higher value (e.g., '3 - Advanced' or '4 - Expert') using the LCP.

  3. 3

    Ensure the drive is in a stopped state (motor not running, output frequency 0 Hz) before attempting to write to critical parameters.

  4. 4

    Check for any active drive functions (e.g., autotuning via Parameter 8-00) that might temporarily restrict write access.

  5. 5

    If the parameter is password-protected, use the LCP to enter the correct password before the Modbus master attempts to write.

Browse all codes in this manual (51)
Verified technical data. Last updated: March 2026

Related Faults

Source: Danfoss VLT Micro Drive FC 51