Danfoss · VLT 2800 Variable Speed Drive
The output frequency has reached either the low limit (parameter 201) or high limit (parameter 202). This warning indicates the drive is operating at its frequency boundaries, potentially unable to maintain the desired process speed. It activates in the display unless in 'Process regulation, closed loop' mode, where it only sets a status bit.
Click steps to track your progress.
Verify the commanded frequency reference value (e.g., analog input voltage/current, fieldbus command) is within the expected operating range.
Check and adjust drive parameters P201 (minimum frequency) and P202 (maximum frequency) to match the required process operating range.
Review and potentially increase acceleration (P207) and deceleration (P208) ramp times if the drive is hitting limits during speed changes.
If using a PID controller, check PID tuning parameters (e.g., P, I, D gains) to prevent overshooting or undershooting the setpoint, which could drive the frequency to limits.
Inspect the mechanical system for binding, excessive load, or other issues that might prevent the motor from reaching or maintaining the desired speed.
Verify the analog input scaling parameter (e.g., P502 for 0-10V, P503 for 4-20mA) matches the connected control signal and desired frequency range.