Danfoss · VLT 2800 Variable Speed Drive
This communication fault specifically occurs in Profibus versions of the drive. It indicates a problem with data exchange over the Profibus network via the HPFB option card.
Click steps to track your progress.
Verify the Profibus GSD file used in the PLC project matches the specific HPFB option card version in the drive.
Check the drive's Profibus address (P801) and baud rate (P802) against the PLC configuration. Ensure no duplicate addresses on the bus.
Inspect the Profibus cable for continuity, shorts, and proper shielding connections from the HPFB card to the network segment.
Confirm that Profibus termination resistors are correctly installed and enabled/disabled at the physical ends of the Profibus segment.
Check the Profibus master (PLC) diagnostic buffer for specific communication errors related to the drive's address.
Use a Profibus diagnostic tool (e.g., ProfiTrace) to analyze bus telegrams, identify signal integrity issues, and locate faulty nodes or segments.