35

Inrush fault

Danfoss · VLT 2800 Variable Speed Drive

What does 35 mean?

This alarm appears when the adjustable frequency drive has been connected to the AC line supply too many times within a short period (1 minute). This typically indicates repeated power cycling that can stress internal components.

Common Causes

  • Repeated power cycling (ON/OFF) of the AC line supply to the drive within a very short timeframe (e.g., manual switch, contactor chatter).
  • External control system (PLC, relay) attempting to reset a temporary fault by cycling drive power instead of using a proper software reset command.
  • Intermittent power supply issues causing brief power outages and immediate reapplication of AC voltage.
  • Large capacitor banks or other high-inrush loads on the same AC line causing voltage sags that trigger protection circuits.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Immediately cease all manual power cycling attempts of the drive's AC input supply.

  2. 2

    Inspect the main input contactor (if present) for proper operation; check auxiliary contacts for reliability and ensuring it isn't chattering.

  3. 3

    Review the control logic (PLC program, relay logic) that controls the drive's AC input power; ensure a minimum delay (e.g., 5 minutes) is implemented between power cycles.

  4. 4

    Measure the AC line voltage at the drive's input terminals (L1, L2, L3) during operation to detect intermittent sags or drops using a logging multimeter.

  5. 5

    Allow the drive's internal inrush current limiting circuit (e.g., precharge resistors) adequate time to cool and reset before reapplying power.

  6. 6

    If an external circuit is used for power ON/OFF, ensure it provides a stable and continuous connection rather than repeated pulses.

Browse all codes in this manual (40)