An error has been detected in the calibration constants stored in the EEPROM. These constants are vital for accurate measurement and control, and any discrepancy can lead to incorrect drive outputs, poor motor control, or misinterpretation of sensor data. This suggests data corruption or a hardware issue with the EEPROM.
Click steps to track your progress.
1. Re-perform the drive's specific calibration procedure for current, voltage, or feedback (e.g. Parameter P7-10 = 1 for auto-calibration).
2. Verify the accuracy of external measurement devices (e.g., current transformers, voltage sensors) connected to the drive's inputs.
3. Measure the actual input voltage at the drive's L1, L2, L3 terminals and compare to the drive's measured value shown in diagnostics.
4. If re-calibration fails, reset the drive to factory defaults (P1-00 = 1) and attempt recalibration.
5. Replace the control card if calibration constant errors persist after multiple attempts and input verification.