Danfoss · VLT 2800 Variable Speed Drive
This fault indicates an inconsistency in the registered motor data that prevents successful Automatic Motor Tuning (AMT). The drive's internal checks have found a mismatch between the provided motor parameters and expected values, which can lead to incorrect motor characterization and suboptimal performance.
Click steps to track your progress.
1. Cross-reference all motor nameplate parameters (P3-01 Motor rated power, P3-02 Motor rated current, etc.) against the motor's physical label.
2. Ensure the entered motor voltage (P3-03) matches the actual supply voltage configuration for the motor.
3. Reset all motor parameters to default values (P3-00 = 0) and re-enter them carefully from the nameplate.
4. Verify that the drive's rated output current and voltage are appropriate for the connected motor's ratings.
5. If using a custom or specialty motor, ensure it meets the drive's general motor compatibility specifications.