Danfoss · VLT 2800 Variable Speed Drive
The DC bus voltage (VDC) has dropped below the 'Voltage warning low' limit. The motor continues to operate, but if the VDC remains low for 2-25 seconds, the inverter will trip with an Alarm 8 (Undervoltage). This can be caused by an insufficient supply voltage or an unstable power source.
Click steps to track your progress.
1. Measure the incoming AC line voltage (phase-to-phase) at terminals R, S, T and compare to the drive's rated input voltage; report any sustained undervoltage to facility maintenance.
2. Power down the drive, then inspect and re-torque all incoming power connections (R, S, T) for looseness or corrosion.
3. Check for any transient voltage sags on the input power by monitoring with a power quality analyzer during operation.
4. Verify that the motor load is not excessive or causing instantaneous overcurrent, leading to bus voltage sag.
5. Review parameter P1-29 (Low Voltage Warning) to ensure it is appropriately set relative to the expected minimum supply voltage.