#14

Earth (ground) fault

Danfoss · VLT AutomationDrive FC 301/302

What does #14 mean?

An earth (ground) fault has been detected, indicating an unintended current path from a phase conductor to the ground. This usually points to damaged insulation in the motor windings or associated cabling, posing a significant safety hazard and a risk of severe damage to the drive or compressor components.

Common Causes

  • Motor winding insulation breakdown due to aging, moisture ingress, or overheating, creating a direct path from a phase to the motor frame.
  • Damaged motor cable insulation (e.g., crushed, abraded, cut) creating a short circuit path from a phase conductor to ground.
  • Water or conductive dust contamination within the motor terminal box or drive enclosure causing a conductive path to ground.
  • Faulty surge arrestor or line filter component (e.g., MOV, Y-capacitor) shorting to ground within the drive or input filter.
  • Improper termination of shielded cables where the shield makes unintended contact with a phase conductor due to incorrect installation.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Isolate power, disconnect motor cables from the drive, and perform an insulation resistance test (Megger) between each motor phase (U, V, W) and motor frame ground (PE). Values should be >1 MΩ.

  2. 2

    Perform an insulation resistance test (Megger) on the motor cables from the drive output to the motor, between each phase and the cable shield/ground conductor.

  3. 3

    Visually inspect the motor terminal box and drive output terminals for signs of arcing, moisture, or conductive debris accumulation.

  4. 4

    Check the integrity of the motor cable conduit and glands for any signs of mechanical damage that could compromise insulation integrity.

  5. 5

    Temporarily disconnect any peripheral devices or filters connected to the motor circuit (e.g., braking resistors, dV/dt filters) and re-test for the fault.