Danfoss · VLT HVAC Basic FC 101
A direct short circuit condition has been detected either within the motor's windings or across its terminal connections. This is a highly critical fault that triggers a trip-lock, requiring a power cycle to reset after the cause is rectified. Operating with a short circuit can cause immediate and irreparable damage to the frequency converter's IGBTs or other power components.
Click steps to track your progress.
Power off the drive and disconnect input power. Disconnect motor cables from drive output terminals (U, V, W).
Measure resistance between each pair of motor phase terminals (U-V, V-W, W-U) at the motor. All three readings should be similar and low (e.g., < 1 Ohm for large motors).
Visually inspect the motor terminal box for loose wires, metallic debris, or damaged insulation between phases.
Perform an insulation resistance test (megger) phase-to-phase and phase-to-ground on the motor windings.
If motor and cable tests are clear, a drive internal fault is likely. Contact authorized service personnel for internal diagnosis.