Danfoss · VLT HVAC Basic FC 101
A high back EMF voltage has been detected, indicating that the Permanent Magnet (PM) motor is rotating while the drive is attempting to control or start it. This can interfere with the drive's control algorithms and prevent a successful start.
Click steps to track your progress.
Verify motor shaft is mechanically stationary before issuing a run command using a visual inspection or a handheld tachometer.
Check Parameter P1-80 ('Flying Start') setting; ensure it is enabled (e.g., set to 'Auto' or 'Enable') to allow controlled startup into a rotating motor.
Measure the AC voltage across motor terminals U, V, W while the drive is stopped; investigate if significant voltage is present, indicating external rotation.
Inspect and test the operation of any external mechanical brake; confirm it fully engages and holds the motor stationary when the drive is not running.
Verify continuity and proper shielding of the motor feedback cable at the drive's respective input terminals (e.g., X33/X34 for encoder).