Danfoss · VLT HVAC Basic FC 101
The motor phase V connection between the frequency converter and the motor is missing or interrupted. This prevents proper motor operation and can lead to damage if ignored.
Click steps to track your progress.
Power off the drive and disconnect input power. Visually inspect and tighten connections for the V-phase motor cable at both the drive's V output terminal and the motor's V terminal.
Measure the resistance of the V-phase motor cable conductor from the drive end to the motor end to check for continuity (expect < 1 Ohm).
With motor cables disconnected from the drive, measure the resistance between motor terminals V-U, V-W, and U-W. All three values should be balanced and low.
Check for any external fusing or contactors in the V-phase motor circuit for continuity and proper operation.
If cable and motor are verified good, the fault indicates a potential internal drive hardware issue with the V-phase output.