Danfoss · VLT HVAC Basic FC 101
The settings for motor voltage, motor current, or motor power are presumably incorrect. This prevents the Automatic Motor Adaptation (AMA) function from accurately identifying motor parameters, leading to suboptimal or incorrect motor control.
Click steps to track your progress.
Compare the motor nameplate data (nominal voltage, current, power) with parameters P1-20, P1-21, P1-22.
Verify the motor connection type (star or delta) matches the setting in P1-10 (Motor Connection).
Ensure no mechanical load is coupled to the motor shaft during the AMA process.
Check for any auxiliary devices (e.g., brakes, heaters) connected to the motor terminals that might interfere with current sensing.
Reset drive to factory defaults (P14-22 = 1 or 2) then re-enter motor data and retry AMA.