Danfoss · VLT HVAC Basic FC 101
The Automatic Motor Adaptation (AMA) process was interrupted by the user. This is not an error but an indication that the parameter identification sequence was not completed, meaning the drive may not be optimally tuned for the motor.
Click steps to track your progress.
Confirm that the AMA process was intentionally interrupted; if not, identify the source of the unintended stop command.
Verify no external safety circuits (e.g., Emergency Stop, safety relays) are tripping during AMA.
Check the state of digital inputs (DI) configured for stop functions on terminals (e.g., DI1, DI2, DI3) with a multimeter.
Inspect the input power supply to the frequency converter for stability and interruptions during AMA.
Restart the AMA process ensuring no external commands or interruptions occur until completion.