ALARM 56

AMA interrupted by user

Danfoss · VLT HVAC Basic FC 101

What does ALARM 56 mean?

The Automatic Motor Adaptation (AMA) process was interrupted by the user. This is not an error but an indication that the parameter identification sequence was not completed, meaning the drive may not be optimally tuned for the motor.

Common Causes

  • User pressed the STOP button or issued a drive halt command (e.g., via LCP or digital input) during the AMA sequence.
  • External interlock tripped (e.g., safety circuit, E-stop, safety gate) during AMA, causing the drive to stop.
  • Loss of control signal (e.g., digital input, fieldbus command) configured to stop the drive during the process.
  • Power supply interruption to the drive or control card during AMA.
  • Fault occurred in an external system (e.g., PLC, HMI) sending an unexpected stop command.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Confirm that the AMA process was intentionally interrupted; if not, identify the source of the unintended stop command.

  2. 2

    Verify no external safety circuits (e.g., Emergency Stop, safety relays) are tripping during AMA.

  3. 3

    Check the state of digital inputs (DI) configured for stop functions on terminals (e.g., DI1, DI2, DI3) with a multimeter.

  4. 4

    Inspect the input power supply to the frequency converter for stability and interruptions during AMA.

  5. 5

    Restart the AMA process ensuring no external commands or interruptions occur until completion.

Browse all codes in this manual (40)
Verified technical data. Last updated: April 2026

Related Faults

10Motor overload temperature11Motor thermistor overtemperature13Overcurrent
Source: Danfoss VLT HVAC Basic FC 101