Danfoss · VLT HVAC Basic FC 101
The temperature on the frequency converter's power card is outside its acceptable operating range (either too high or too low). Extreme temperatures can lead to premature component failure or immediate drive shutdown to prevent damage.
Click steps to track your progress.
Check the drive's cooling fan operation; verify it spins freely and replace if seized or noisy.
Inspect all cooling air vents and heatsinks for dust, debris, or blockages, and clean them thoroughly.
Measure the ambient air temperature inside the control cabinet and around the drive; ensure it is within specified limits.
Verify motor nominal current (P1-21) and motor nominal power (P1-22) are correctly set, and AMA has been performed.
Ensure the drive is not undersized for the application, leading to continuous high current draw.
For low temperature, consider adding cabinet heating or temporary shielding for cold startup.