Danfoss · VLT HVAC Basic FC 101
No motor is detected as connected to the output of the frequency converter. This condition prevents the drive from operating and indicates a potential wiring issue or a missing motor connection.
Click steps to track your progress.
With power off, measure the resistance between the drive's output terminals U, V, W (or L1, L2, L3 for single-phase) to verify continuity and balanced phase resistance (typical 0.1-100 Ohms).
Verify all motor power cable connections are secure and properly terminated at both the drive's output terminals (e.g., T1, T2, T3) and the motor terminal box.
Disconnect the motor power cables from the drive and measure the winding resistance directly at the motor terminals (U-V, V-W, W-U); ensure readings are balanced.
If an external motor output contactor is installed, check its coil for proper energization (e.g., 24VDC) and confirm its main power contacts close when a run command is active.
Ensure that the drive's motor data parameters (e.g., P1-20 'Nominal Voltage', P1-22 'Nominal Current', P1-23 'Nominal Speed') are accurately entered for the connected motor.