The data type of the value being written (e.g., integer, float, text) through Holding Register 0007 does not match the expected data type of the parameter being called. This can lead to data corruption, misinterpretation, or a failure to apply the new setting correctly.
Click steps to track your progress.
Consult the drive's communication manual for the specific parameter to confirm its exact data type (e.g., integer, float, enumerated type).
Review the Modbus master's program (e.g., PLC code, HMI driver) to ensure the value being sent to Holding Register 0007 is converted to the correct data type.
Ensure correct byte order and word handling (e.g., for 32-bit values often requiring two 16-bit Modbus registers) is implemented in the Modbus master.
If the parameter is an enumerated type (e.g., 'ON', 'OFF', 'AUTO'), ensure the numerical equivalent (e.g., 0, 1, 2) is being sent, not the text string.
Temporarily use a Modbus scanner tool to manually write known correct data types (e.g., 16-bit integer) to the parameter to isolate the issue.