Danfoss · VLT Micro Drive FC 51
An earth fault (ground fault) has been detected in the motor or the cabling between the drive and the motor. This indicates current leakage to ground, which is a serious safety hazard and can cause significant damage to the drive or motor if not resolved promptly.
Click steps to track your progress.
Disconnect the motor cables from the drive's output terminals (U, V, W) and then power cycle the drive to see if the fault clears.
Perform an insulation resistance test (Megger test) on the motor windings to earth (motor frame) with a 500VDC Megger, expecting >1 Megaohm.
Perform an insulation resistance test on each motor cable phase (U, V, W) to earth along the entire cable run with a 500VDC Megger.
Visually inspect the motor terminal box for moisture, corrosion, or signs of arcing.
Check continuity between the motor frame and the main earthing point of the control cabinet.