Danfoss · VLT Micro Drive FC 51
The Automatic Motor Tuning (AMT) process detected an incorrect setting for the motor's nominal voltage and/or nominal current parameters. This prevents accurate motor modeling and can lead to suboptimal motor control, protection, and efficiency.
Click steps to track your progress.
Verify the motor's nameplate data (Volts, Amps, RPM, kW/HP) and compare it against the drive's parameter settings (P1-20, P1-22, P1-23, P1-25).
Confirm the motor's terminal connection (Star/Delta) matches the supplied mains voltage and the motor's rated voltage.
Measure the actual input mains voltage to the drive and ensure it is within the drive's specified operating range.
Inspect all motor cable connections at both the drive's output terminals and the motor's terminal box for secure contact.
Rerun the Automatic Motor Tuning (AMT) process (e.g., Parameter P1-29) after verifying and correcting all motor parameters.