Danfoss · VLT Micro Drive FC 51
The drive has reached its internal current limit due to an overload condition, similar to 'Inverter overloaded' but possibly indicating a different internal control loop limitation. This is a protection mechanism to prevent damage to the drive's power components.
Click steps to track your progress.
Measure the actual motor current (via LCP display P06-00) during operation and compare it against the motor's nameplate nominal current.
Inspect the mechanical load connected to the motor for any binding, jamming, or excessive friction that could cause overload.
Verify that the motor's nominal current (P1-23) is accurately set in the drive based on the motor nameplate.
Increase the acceleration ramp time (P1-41) to allow for a slower current build-up during startup of high inertia loads.
Monitor DC bus voltage (LCP display P06-01) during acceleration to rule out input voltage sag contributing to higher current draw.