This warning suggests that the drive is operating in a condition where it needs to reduce its output frequency or torque to maintain stable operation, often due to exceeding a current or voltage limit. While not an immediate trip, continued operation under these conditions can lead to a trip or reduced performance.
Click steps to track your progress.
Monitor the drive's output current (e.g., via Parameter P0-03) and compare it against the motor's rated current and drive's nominal current.
Measure the AC input voltage at the drive's L1, L2, L3 terminals under load to detect voltage sags.
Verify the motor's mechanical load by manually checking for friction or obstructions.
Check the drive's heatsink temperature (e.g., Parameter P0-15) and ensure adequate ventilation in the control cabinet.
Increase the current limit (Parameter P1-08) if the application legitimately requires higher peak current, but ensure motor protection is maintained.