An attempt was made to change a parameter that can only be modified when the motor is stopped. This protection mechanism prevents configuration changes that could cause instability, erratic behavior, or damage to the motor or driven equipment during operation.
Click steps to track your progress.
Issue a stop command to the drive and confirm the motor has completely stopped (output frequency 0 Hz) before attempting parameter modification.
Verify the drive is in a ready state (not running or faulted) by checking the LCP display or drive status register (e.g., Parameter 16-10).
If modifications are frequent, consider using parameters that allow 'Online' changes (if available) or plan maintenance windows for changes.
Ensure that no run commands are active on control terminals (e.g., Terminal 18, 'Start') or via communication (e.g., Modbus bit 0 in control word) while making changes.
Temporarily set Parameter 1-00 (Control Mode) to a basic configuration if advanced modes are preventing parameter changes while stopped.