The regenerative discharge unit has overheated, typically triggered when the average regenerative discharge energy is excessively high, such as during frequent acceleration/deceleration cycles. This can also indicate connection issues or component failure within the unit.
Click steps to track your progress.
For SVM1-4i/SVM1-20i (without separate unit): Check if the CXA20 connector is short-circuited with a dummy connector.
For SVM1-40i/SVM1-80i (without separate unit): Check if the CXA20 and CZ6 connectors are short-circuited with dummy connectors.
Decrease the acceleration/deceleration frequency to reduce average regenerative discharge energy.
Verify the physical connection of the separate regenerative discharge unit.
Disconnect the separate regenerative discharge unit; check the thermostat. If the thermostat is open when the unit is cool, replace the unit.
Disconnect the separate regenerative discharge unit; measure its resistance. If it is not within ±20% of the predetermined resistance, replace the unit.