Fanuc · Alpha i series AC Servo Motor
A DC Link Low Voltage Alarm has been issued, indicating that the DC voltage of the main circuit power is too low. This can result from insufficient supply voltage, issues with external contactors, or delayed power-up sequences.
Click steps to track your progress.
Verify the operating time of the external magnetic contactor. Ensure it turns on within 100 ms after *ESP signals are canceled.
Check the status of the external circuit breaker.
Measure the supply voltage for dynamic power. If too low, increase it to an appropriate level.
Check the physical connection of the external magnetic contactor.
If all other steps fail, replace the servo amplifier unit.