Alarm 2

Software Disconnection (Closed Loop)

Fanuc · Alpha i Series Servo Amplifier

What does Alarm 2 mean?

This alarm is issued when the change in position feedback pulses is relatively small for the change in velocity feedback pulses. This condition typically occurs in a closed-loop system and is not issued with the semi-closed loop.

Common Causes

  • The closed-loop control system has lost its feedback signal.
  • Software error preventing the system from establishing a closed loop.
  • Encoder or sensor is not providing valid position data.
  • Communication failure with the position feedback device.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check whether the separate detector outputs position feedback pulses correctly.

  2. 2

    If the detector outputs pulses correctly, investigate for a large backlash between the motor position and scale position causing reverse rotation of only the motor at the start of machine operation.