Alarm 5

System Alarm: Feedback Mismatch, Semi-Closed Loop Error, or Current Offset Error

Fanuc · Alpha i Series Servo Amplifier

What does Alarm 5 mean?

This alarm can indicate multiple issues depending on the set bits. If the OFS bit is set, it is a Feedback Mismatch alarm, suggesting opposite move directions for the position and velocity detectors. Other bits include MCC for Excessive Semi-Closed Loop Error and LDM for Current Offset Error.

Common Causes

  • Discrepancy between commanded position and actual feedback position.
  • Error detected in a semi-closed loop configuration.
  • The current offset of the motor is outside acceptable limits.
  • Feedback signal from the encoder or sensor is unreliable.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    If the OFS bit is set (Feedback mismatch alarm), check the rotation direction of the separate detector.

  2. 2

    If the separate detector's direction is opposite to the motor's rotation: For a Phase A/B detector, reverse the A and __A connections.

  3. 3

    If the separate detector's direction is opposite to the motor's rotation: For a Serial detector, reverse the signal direction setting for the separate detector.

  4. 4

    For Series 90B0/07 and subsequent editions, verify the setting that allows the signal direction to be reversed even for the phase A/B detector.

Browse all codes in this manual (101)
Verified technical data. Last updated: April 2026

Related Faults

0233Velocity Pulse Count Exceeded0243Position Pulse Count Exceeded0434Velocity Loop Integral Gain Overflow
Source: Fanuc Alpha i Series Servo Amplifier
Open Manual (Page 46)Search more codes in this manual